- Main
- Product Catalog
- Power cables with plastic insulation with a rated voltage of up to 3 and 6 kilovolts
- VVGNG (A) -FRLS, VVGENG (A) -FRLS, VBSHVNG (A) -FRLS, VVG-PNG (A) –FRLS
VVGNG (A) -FRLS, VVGENG (A) -FRLS, VBSHVNG (A) -FRLS, VVG-PNG (A) –FRLS
![](/uploads/ncat/a-frhf-ppgenga-frhf-pvpgnga-frhf-pvpgenga-frhf_preview.png)
Applying area and purpose
Cables are designed for transmission and distribution of electric energy in stationary electrical installations at a rated alternating voltage of 0.66 and 1 kV with a frequency of 50 Hz or a constant voltage of 1 and 1.5 kV.
Cables are used for group cabling of power supply lines for electrical equipment of security systems, electrical wiring of fire safety systems, electrical wiring in hospital operating rooms, emergency power supply circuits and power equipment operating in case of fire.
Cables are also used at nuclear power plants (AS) outside the containment zone in Class 2 AS systems according to the classification of OPB 88/97 (PNAE G-01-011).
Fire hazard class of cables according to NATIONAL QUALITY STANDARD 31565 P1b.1.2.2.2
Technical data
Rated voltage, kV | 0,66 or 1 | |
Ambient temperature during cable use °С | from -50 to +50 | |
Minimum bending radius cable diameters |
For multi-core | 7,5 |
For single core and flat | 10 | |
Cables are laid at a temperature (without preheating), ° С, not lower | -15 | |
Flammability of cables, min, not less | 180 | |
Smoke in the test chamber | Not more then 50% |
Conductive core
Copper, single-wire or multi-wire, round or sector shape, class 1 or 2 according to NATIONAL QUALITY STANDARD 22483 with a cross section from 1.5 to 400 mm2.
Thermal barrier according to thermal conductivity
A winding of two mica tapes.
Insulation
PVC compound of reduced fire hazard.
Twisting
Insulated conductors of 2, 3, 4 and 5 core cables are twisted into a core. In VVG-Png (A) -FRLS cables, the conductors are parallel in the same plane.
Inner shell
PVC compound of reduced fire hazard.
Screen
For cables of the VVGENG (A) -FRLS brand, it is made in the form of a winding made of copper tapes or copper foil;
Outer shell
PVC compound of reduced fire hazard.