- Main
- Product Catalog
- Power cables with plastic insulation with a rated voltage of up to 3 and 6 kilovolts
- VVG-PNG (A), AVVG-PNG (A)
VVG-PNG (A), AVVG-PNG (A)
Applying area and purpose
Cables are designed for transmission and distribution of electric energy in stationary electrical installations at a rated alternating voltage of 0.66 and 1 kV with a frequency of 50 Hz
For single installation in cable structures and rooms. Cables VVG-PNG (A), AVVG-PNG (A) are not recommended for laying in the ground (trenches).
Fire hazard class of cables according to NATIONAL QUALITY STANDARD 31565 O1.8.2.5.4.
Technical data
Rated voltage, kV | 0,66 or 1 |
Ambient temperature during cable use | from - 50 of +50 |
Minimum bending radius cable diameters | 10 |
Cables are laid at a temperature (without preheating), ° С, not lower | -15 |
Conductive core
Copper or aluminum single wire, round, class 1, according to NATIONAL QUALITY STANDARD 22483.
Number of cores 2 and 3
Nominal section of the main veins, mm2
Copper 1.5 - 16
Aluminum 2.5 - 16
Insulation
PVC compound (color cores).
Location of veins
Insulated cores are laid parallel in one plane.
Outer shell
Low flammability PVC compound.