VVG-P, AVVG-P

Description Construction

Applying area and purpose

Cables are designed for transmission and distribution of electric energy in stationary electrical installations at a rated alternating voltage of 0.66 and 1 kV with a frequency of 50 Hz

For single installation in cable structures and rooms. Cables VVG-P, AVVG-P are not recommended for laying in the ground (trenches).

Fire hazard class of cables according to NATIONAL QUALITY STANDARD 31565 O1.8.2.5.4.

Technical data 

Rated voltage, kV

0,66 or 1

Ambient temperature during cable operation, °С

from  - 50

to + 50

Minimum bending radius, cable diameters (smallest measurements)

10

Cables are laid at a temperature (without preheating), ° С, not less

- 15

Conductive core

Copper or aluminum, single-wire, round shape, 1 class according to national quality standard 22483.

Number of cores 2 and 3

Nominal section of the main veins, mm2 Copper 1.5 - 16

Aluminum 2.5 - 16

Insulation

PVC compound (color cores).

Location of veins

Insulated cores are laid parallel in one plane.

Outer sheath PVC compound.

Other products

VVG, AVVG, VVGE, AVVGE, VBBSHV, AVBBSHV
Сonductive core Copper or aluminum, single-wire or multi-w...
PVVG, APVVG, PVVGE, APVVGE, PVBSHV, APVBSHV, PVVG-P, APVVG-P, PVBSHP, APVBSHP
Conductive core Copper or aluminum, single-wire or multi-w...
VVGNG (A), AVVGNG (A), VVGENG (A), AVVGENG (A), VBSHVNG (A), AVBSHVNG (A)
...