VVG-P, AVVG-P
Applying area and purpose
Cables are designed for transmission and distribution of electric energy in stationary electrical installations at a rated alternating voltage of 0.66 and 1 kV with a frequency of 50 Hz
For single installation in cable structures and rooms. Cables VVG-P, AVVG-P are not recommended for laying in the ground (trenches).
Fire hazard class of cables according to NATIONAL QUALITY STANDARD 31565 O1.8.2.5.4.
Technical data
Rated voltage, kV |
0,66 or 1 |
Ambient temperature during cable operation, °С |
from - 50 to + 50 |
Minimum bending radius, cable diameters (smallest measurements) |
10 |
Cables are laid at a temperature (without preheating), ° С, not less |
- 15 |
Conductive core
Copper or aluminum, single-wire, round shape, 1 class according to national quality standard 22483.
Number of cores 2 and 3
Nominal section of the main veins, mm2 Copper 1.5 - 16
Aluminum 2.5 - 16
Insulation
PVC compound (color cores).
Location of veins
Insulated cores are laid parallel in one plane.
Outer sheath PVC compound.