PVKV, APVKV, PVKAV, APVKAV PVKVNG (A), APVKVNG (A), PVKAVNG (A), APVKAVNG (A) PVKVNG (A) -LS, APVKVNG (A) -LS, PVKAVNG (A) -LS, APVKAVNG (A) -LS

Description Construction

Applying area and purpose

  • Cables are designed for transmission and distribution of electrical energy in stationary installations for a rated alternating voltage of 6-35 kV with a nominal frequency of 50 Hz for networks with a grounded and insulated neutral;
  • For laying in the ground (in trenches) where protection against mechanical damage is required;
  • Designed for operation when laying in the ground, regardless of the degree of corrosion activity of soils;
  • For laying along routes of complex configuration.
  • Cables made by ng (a) -ls are used for laying:
  • - in bundles
  • - at facilities where requirements for reduced smoke and gas emissions are imposed (nuclear power plants, subways, large industrial facilities, high-rise buildings, etc.)

Technical data

Rated voltage, kV

6-35

Ambient temperature during cable operation,° C

from  - 50

up to + 60

Ambient temperature for laying without preheating, C, not lower

-10

Permissible core heating temperature:

  • in normal mode
  • in emergency mode
  • in short circuit mode

 

90°С

130°С

250°С

The maximum permissible temperature of the screen during short circuit

350°С

Minimum bending radius of cables

15

Minimum bending radius of cables

5 pC

Maximum allowable traction force when laying

  • For copper position
  • For aluminum position

 

 

50 N / mm²
30 N / mm²

 

Test voltage (50 Hz)

3.5U0.5min

  • One round sealed stranded conductive aluminum / copper core;
  • Screen on the core of extrudable semiconducting cross-linked polyethylene;
  • XLPE Insulation;
  • Screen for insulation from extrudable semiconducting cross-linked polyethylene;
  • Separating layer of semiconducting crepe paper tape;
  • Screen made of copper wires fastened with copper tape;
  • Separating layer of glass tape;
  • Pillow for armor made of PVC compound, low flammability polyvinyl chloride for ng (A) and low fire hazard PVC compound for ng (A) –LS
  • Shell:
  • - from polyvinyl chloride plastic compound
  • - of low flammability polyvinyl chloride plastic compound for ng (A)
  • - from PVC compound of reduced fire hazard for the ng (A) -LS category.

Other products

VVG, AVVG, VVGE, AVVGE, VBBSHV, AVBBSHV
Сonductive core Copper or aluminum, single-wire or multi-w...
VVG-P, AVVG-P
Conductive core Copper or aluminum, single-wire, round sha...
PVVG, APVVG, PVVGE, APVVGE, PVBSHV, APVBSHV, PVVG-P, APVVG-P, PVBSHP, APVBSHP
Conductive core Copper or aluminum, single-wire or multi-w...